6EP1732-0AA00
SITOP POWER 2, СТАБИЛИЗИР. БЛОК ПИТАНИЯ УНИВЕРСАЛЬНОЙ ЛИНИИ: ГАЛЬВАН. РАЗД. ВХОДНЫХ И ВЫХОДНЫХ ЦЕПЕЙ..
Цена: по запросу
Преобразователь DC-DC

Order No.

6EP1732-0AA00

Product

SITOP power

Power supply, type

24 V/2 A

Input

-

Input

DC

Voltage range min.

-

Voltage range max.

-

Supply voltage

 

  • 1 for AC

 

    • Minimum rated value

-

    • Maximum rated value

-

  • 2 for AC

 

    • Minimum rated value

-

    • Maximum rated value

-

  • 1 for AC rated value

-

  • 2 for AC rated value

-

  • for DC

48 ... 110 V

Note

-

Input voltage

 

  • 1 for AC

 

    • Initial value

-

    • End value

-

  • 2 for AC

 

    • Initial value

-

    • End value

-

  • for DC

38 ... 121 V

Wide-range input

Yes

Overvoltage strength

-

Mains buffering at Iout rated, min.

5 ms

Mains buffering

at Uin = 48 V

Rated line frequency

 

  • 1

-

  • 2

-

Line frequency range  min.

-

Line frequency range  max.

-

Input current

 

  • at rated value of the input voltage 120 V rated value

-

  • at rated value of the input voltage 230 V rated value

-

  • at rated value of the input voltage 24 V rated value

-

  • at rated value of the input voltage 48 V rated value

1.2 A

  • at rated value of the input voltage 110 V rated value

0.5 A

  • at rated value of the input voltage 220 V rated value

-

  • at rated value of the input voltage 400 V rated value

-

  • at rated value of the input voltage 420 V rated value

-

  • at rated value of the input voltage 500 V rated value

-

Switch-on current limitation (+ 25°C), max.

33 A

Duration of the switch-on current limitation at 25°C

 

  • Typical

-

  • Maximum

-

I²t, max.

-

Built-in line-side fuse

T 2.5 A (not accessible)

Protection in the main supply conductor (IEC 898)

Recommended miniature circuit-breaker: 10 to 25 A, characteristic B or 6 to 25 A, characteristic C, suitable for DC

Output

-

Output

Controlled, isolated DC voltage

Rated voltage Uout rated DC

24 V

Total tolerance, static ±

1%

Static line compensation, approx.

0.1%

Static line compensation, approx.

0.4%

Residual ripple, peak-peak, max.

0.1 V

Residual ripple, peak-peak, typ.

-

Spikes, peak-peak, max. (bandwidth approx. 20 MHz)

0.3 V

Spikes, peak-peak, max. (bandwidth approx. 20 MHz)

-

Adjustment range

23.5 ... 26.5 V

Product function: output voltage is adjustable

Yes

Adjustment of the output voltage

via potentiometer

Note

-

Status indicator

Green LED for 24 V OK

Signaling

-

On/Off behavior

Overshoot of Uout on startup max. 25 V

ON delay, max.

3 s

Voltage rise, typ.

30 ms

Maximum voltage rise time of the output voltage

-

Rated current Iout rated

2 A

Current range

0 A

Current range up to +55°C

2 A

Note

-

Active power output, typical

48 W

Short-term overload current in the event of a short-circuit during power-up, typical

-

Duration of the overload capability overcurrent at short-circuit during power-up

-

Constant overload current in the event of a short-circuit during power-up, typical

-

Short-term overload current in the event of a short-circuit during operation, typical

-

Duration of the overload capability  overcurrent in the event of a short-circuit during operating phase

-

Constant overload current in the event of a short-circuit during operation, typical

-

Parallel switching for enhanced performance

Yes

Note

-

Number of devices that can be switched in parallel to increase performance, units

2

Efficiency

-

Efficiency at Uout rated, Iout rated, approx.

84%

Efficiency at Uout rated, Iout rated, approx.

9 W

Closed-loop control

-

Dyn. line compensation (Uin rated ±15%), max.

0.3%

Dyn. load compensation (Iout: 50/100/50%), Uout ± typ.

0.8%

Load-step settling time 50 to 100%, typ.

2.5 ms

Load-step settling time 100 to 50%, typ.

2.5 ms

Settling time, maximum

-

Protection and monitoring

-

Output overvoltage protection

Yes, suppressor diode at output

Current limitation

2.1 ... 3 A

Current limitation, typ.

-

Property of the output, short-circuit-proof

Yes

Short-circuit protection

Electronic shutdown, automatic restart

Sustained short-circuit current rms value

 

  • Maximum

2 A

  • Typical

-

Note

-

Overload/short-circuit indicator

-

Safety

-

Primary/secondary isolation

Yes

Electrical isolation

Safety extra-low output voltage Uout to EN 60950-1

Protection class

Class I

Leakage current

 

  • Maximum

3.5 mA

  • Typical

0.7 mA

CE mark

Yes

UL/CSA approval

Yes

UL/cUL (CSA) approval

cULus-listed (UL 508, CSA C22.2 No. 142), File E179336

Explosion protection

-

FM approval

No

FM approval

-

CB approval

No

Marine approval

-

Degree of protection (EN 60529)

IP20

EMC

-

Emitted interference

EN 55022 Class B

Supply harmonics limitation

not applicable

Noise immunity

EN 61000-6-2

Operating data

-

Ambient temperature

 

  • during operating phase

0 ... 70°C

Note

with natural convection

Ambient temperature

 

  • during transport

-40 ... +70°C

Ambient temperature

 

  • during storage

-40 ... +70°C

Humidity class to EN 60721

Climate class 3K3, no condensation

Mechanics

-

Connection system

Screw connection

Connections

 

  • Supply input

L+1, M1, PE: 1 screw-type terminal each for 2 x 0.5 ... 2.5/1.5 mm² single-core/finely stranded

  • Output

L+, M: 1 screw-type terminal each for 2 x 0.5 ... 2.5 mm²

  • Auxiliary contacts

-

Width of enclosure

80 mm

Height of enclosure

135 mm

Depth of enclosure

120 mm

Width/mounting dimensions

80 mm

Mounting height

235 mm

Weight, approx.

0.5 kg

Product property of the enclosure: side-by-side enclosure

Yes

Type of mounting

 

  • Wall mounting

No

  • Standard rail mounting

Yes

  • S7-300 DIN rail mounting

No

Mounting

can be snapped onto standard mounting rail EN 60715 35x15

Electrical accessories

-

Mechanical accessories

-

EAN code

4 025515 140320